GAS EXTINGUISHING SYSTEMS

free web creation software
Mobirise

Inert Gas Fire Extinguishing Systems

It is the reaction of naturally occurring inert gases in the atmosphere: Argon, Nitrogen, Carbon dioxide
It is colorless, odorless and not conductive,
ODP = 0 Does not damage ozone / Environment friendly,
GWP = 0 No global warming effect,
It extinguishes by reducing oxygen in the environment.
It does not leave any residue after the discharge, it does not require cleaning.
It can be used safely in human places.
Design for class A fires was 39.9% (NOAEL 43%, LOAEL 52%
It is used in the replacement of Halon 1301 systems.
200 or 300 bar cylinder pressure / 55-60 bar installation pressure.
Standards ISO1450, UNE 23570 & NFPA 2001: IG55
80 & 140 lt capacity can be stocked in cylinders.
Discharge Time: 60 seconds.
Single or multiple cylinders can be used.
A number of rooms can be extinguished from the same center using the guiding valves.
It can be easily found locally and filled in our country.

>> Back to Products and Services <<

Mobirise

Carbon dioxide gas extinguishing systems

It does not damage the ozone layer.
Physically extinguishes.
Can be used for local extinguishing.
It is not used in places where people are.
The re-filling costs are low.
It is colorless, odorless and not conductive.
Usage Areas of System
System design can be done according to the total volume of the protected area, and it is suitable to design as point-local extinguishing system.
It can be used in all class (A), (B), (C) fires, and not in class (D) fires.
In transformer fire extinguishing systems, UPS - uninterruptible power supplies in fire extinguishing systems, cable and plumbing galleries, natural gas distribution stations, HES and thermal power plants, Generator, compressor, ventilation units, ships, cargo, machine room and warehouse, Centers, Factories, Schools and Hospitals etc.

>> Back to Products and Services <<

Mobirise

Novec 1230 Gas Extinguishing Systems

Novec 1230 fire extinguishing systems are ideally suited for special hazard classes, where the operation of high value equipment and electronic systems can not be interrupted, where people are present and at the same time fire safety is very important.

System features
The ozone layer penetration coefficient (ODP) is 0. It has only a 5-day atmospheric lifetime and the greenhouse effect coefficient (GWP) is 1.
According to the UL 2166 test protocol, the Class A firefighting concentration for Novec 1230 is 3.5%. With the same concentration as the Halon 1301, Novec 1230 has been replaced with the Halon 1301 to update its system.
It is very effective in extinguishing electrical and electronic equipment by not having an insulating property and rapidly passing through the gas phase.
Usage Areas of System
UPS - uninterruptible power supplies in fire fighting systems,
In archive fire fighting systems,
In museum fire fighting systems,
In cash registers, in ATM systems, in bank money transport vehicles,
In warehouse fire fighting systems,
In fire extinguishing systems in the chemical sector,
In all electrical and electronic systems,
Generators, compressors, ventilation units,
In ships, in cargo, machine room and stockroom warehouses,
In GSM link stations and cabinets,
At the bank data processing centers, etc.

>> Back to Products and Services <<

Mobirise

Fm 200 Gas Extinguishing Systems

FM-200 is a Halon alternative gas which is put on the market after the ban on the use of Halon 1301 gas and is the most common use.
Chemical name Heptafluoropropane dir. FM 200 vents fires with the ability to break chemical reactions that play an important role in fire and to absorb heat energy.
FM-200 gas extinguishing systems are recommended, especially if at least one of the following conditions exists:
If the value of the material in the protected area or the prosperity in terms of business continuity requires a fire system to move within seconds.
If the sprinkler system will damage the material in the protected area.
If there are people in the protected area; If cleaning after fire is desired to be eliminated If there is a need for easy design and installation.

FM200 Gas System Features
It is colorless, odorless and not conductive.
Does not harm ozone, Atmospheric life is 31-42 years.
Physically extinguishes. No need to clean after dispensing
It can be used safely in people's places. Halon 1301 is the most widely used alternative.
It is economical. It takes up a lot of space. The discharge time is 10 seconds.
FM200 Gas System Components
The FM 200 consists of chemical agent and four major components and accessories of these components.
1. FM-200 Components: consists of cylinder, cylinder holder, and FM-200 discharge nozzle in which the FM-200 gas is stored.
2. Control Panel: The system is the brain, used to view, monitor and activate the detection system and equipment.
3. Detection and Warning Elements: Detection detectors and accessories in the system, sirens giving audible and visual warning, external equipment that performs the eye and ear functions of the system.
4. Complementary Equipments: The warning plates consist of hoses, fittings, pressure manometers or actuators required to operate the solenoid valve and the cylinder valve.
System Design And Operation Sequence
The volume of gas required to be protected by the FM-200, gas is calculated according to the NFPA 12 and ISO 14520 standards and regulations,
The FM 200 tube is selected according to the amount of gas,
The required points in the room equipped with the cross-zone fire detection system are the FM-200 discharge nozzles,
With the smoke detectors active, the FM-200 system sends current to the solenoid valve in a panel,
All FM-200 vents are evacuated to a protected volume within a maximum of 10 seconds. The operation of the system can be done automatically or manually.
Locations Used
Computer rooms, Telephone stations, Tape - disk - diskette warehouses, Telecommunication centers Transformer and power distribution chambers, Generator rooms, Electricity distribution rooms / centers, Valuable material warehouses, Medical and industrial laboratories, System control rooms, Bank cases, Archives, Mills and art galleries, Flammable liquid warehouses, Turbine booths etc.

>> Back to Products and Services <<

© All rights belong to Çillioğlu Fire Fighting and Security Systems. 2018